Indoor Air Quality In A Bus

Price

Free (open access)

Volume

134

Pages

9

Page Range

749 - 757

Published

2014

Size

2,184 kb

Paper DOI

10.2495/SAFE130671

Copyright

WIT Press

Author(s)

A. Gajewski

Abstract

This paper looks at indoor air qualities in a bus. Two experiments were done during an outbound and return journey with 24 passengers plus a driver. The focus of attention was carbon dioxide concentration. The permitted value 1000 ppm of CO2 was exceeded during the trip there and at the beginning of the return journey, the maximum measured concentration was 2400 ppm. The calculations of minimum share of fresh air to provide what was required by the standard conditions were undertaken. Too high CO2 concentration may contribute to dangerous situations on roads. Keywords: carbon dioxide emissions, indoor air quality, bus, travel security.

Keywords

carbon dioxide emissions, indoor air quality, bus, travel security